Form O-CAUA, P/N 164772 R7, Page 3
2.2.1 Blower and
Blower Motor
R
Remove dirt and grease from the motor and the blower. Use care when cleaning
to prevent causing misalignment or imbalance. If the unit is equipped with a belt drive,
check the belt for signs of wear. Replace if needed.
Check the belt tension. Proper belt tension is important to the long life of the
belt and motor. A loose belt will cause wear and slippage. Too much tension
will cause excessive motor and blower bearing wear. Adjust the belt tension
by turning the adjusting screw on the motor base until the belt can be depressed
3/4" (19mm). (See FIGURE 1.) After correct tension is achieved, re-tighten the locknut
on the adjustment screw and recheck belt alignment.
FIGURE 1 - Check Belt
Tension
Code Reason for Maintenance
S
= Safety (to avoid personal injury and/or property damage)
R
= Continued Reliability
E
= Efcient Operation
2.2 Maintenance
Procedures
2.2.2 Filters
R
E
Check the lters quarterly. Clean or replace as needed. Replacement P/N's
for lters are listed here with application by size listed below.
2" Pleated Filters 2" Permanent Filters 2" Disposable Filters
16x16, P/N 104109 16x16, P/N 104103 (Btm Filter Cabinet only)
12x32, P/N 114324 12x16, P/N 114325 16x16, P/N 104101
16x20, P/N 101620 16x20, P/N 101620
1" x 16" x 25" Filters for Inlet Base only (Size 350 and 400 only)
Disposable - P/N 16447; Permanent - P/N 101609; Pleated - P/N 104107
(Applies to a heater
with either an optional
return air lter cabinet;
an outside air/return air
mixing box with lters;
or an inlet base with
lters.)
Sizes & Quantities of Filters Used in Return Air Filter Cabinet
To replace lters, select replacement P/N's from the list above for type and size of l-
ters. If using eld-replacement lters, replace with same size and type.
TABLE 1A -
Replacement Filters
for Return Air Filter
Cabinet
For Full Size Filter Cabinet on
Either Side of the Heater
For Small Filter Cabinet on
Either Side or Rear of Heater
Size Permanent or Pleated
150, 200, 250, 300 (4) 16x16 - 2" Filters
Size CFM FPM
2" Filters
350, 400 (6) 16x16 - 2" Filters Pleated Permanent
For Full Size Filter Cabinet on Rear of Heater
150
1800 375 (2) 12x32 (4) 12x16
Size Permanent or Pleated 2400 500 (2) 12x32 (4) 12x16
150, 200 (4) 16x16 - 2" Filters *3000 625 -- (4) 12x16
250, 300, 350, 400 (6) 16x16 - 2" Filters
200
2400 500 (2) 12x32 (4) 12x16
For Filter Cabinet on Bottom of Heater *3000 625 -- (4) 12x16
Size
Permanent, Pleated, or
Disposable Filters
*Application requires 2" permanent; do not
use pleated lters.
150, 200 (6) 16x16 - 2" Filters
250, 300 (8) 16x16 - 2" Filters
350, 400 (12) 16x16 - 2" Filters
Sizes and Quantities of Filters (1" only) Used in the Optional Inlet Base
(Option AVA2 for Sizes 350 and 400 only)
Each base requires eight lters (or only six if one side is blocked off). Filters are 1" x
16" x 25"; P/N's for each type of lter are listed in the table above.
Sizes and Quantities of Filters (2" Permanent or 2" Pleated only) and
Blockoff Plates Used in the Optional Outside Air/Return Air Mixing Box
To replace lters, select replacement P/N's from the list on page 3 for type and size of
lters in TABLE 1B. If using eld-replacement lters, replace with same size and type.
TABLE 1B - Replacement Filter Quantity and Sizes for Mixing Box
Size Filters - (Qty) Size Filter Blockoff Plate
150, 200 (2) 16 x 16; (2) 16 x 20 (1) P/N 123226
250, 300, 350, 400 (6) 16 x 16 (1) P/N 114337
TABLE 1B -
Replacement Filters
and Blockoff Plates for
Mixing Box