Form I-EEDU, P/N 150492 R6, Page 1Form I-EEDU (Version C.1)Obsoletes Form I-EEDU (Version C)Applies to: Model EEDU Indoor, Power-Vented Duct Furnace
Form I-EEDU, Page 10Manifold or Orice (Valve Outlet) Pressure Settings6.0 Mechanical (cont'd)6.2 VentingVenting must be in accordance with the N
Form I-EEDU, P/N 150492 R6, Page 11Specic Venting Requirements (read all before installing)1. Type of Vent PipeUse either vent pipe approved for a Ca
Form I-EEDU, Page 126.0 Mechanical (cont'd)NOTE 1: If the system contains all vertical pipe or a combination of vertical and horizontal vent pipe
Form I-EEDU, P/N 150492 R6, Page 13FIGURE 10A - Attaching Double-Wall (Type B) Pipe to a Vent CapFigure 10A - STEP 1Place a continual 3/8” bead of sil
Form I-EEDU, Page 146.2 Venting (cont'd)6.0 Mechanical (cont'd)Venting Requirements cont'd)FIGURE 11B - Horizontal Vent Terminal
Form I-EEDU, P/N 150492 R6, Page 156.3.3 Constructing Bypass DuctFIGU
Form I-EEDU, Page 166.0 Mechanical (cont'd)FIGURE 14 - Duct Connection Dimensions - inches (mm)NOTE: If the furnace is eq
Form I-EEDU, P/N 150492 R6, Page 17FIGURE 15A - Connecting Ductwork to the Furnace1) Flanges on the heater turn out as shown. 2) Shape duct connection
Form I-EEDU, Page 187.0 Electrical Supply and Wiring7.1 GeneralAll electrical wiring and connections, including electrical grounding MUST be made in a
Form I-EEDU, P/N 150492 R6, Page 19Line Voltage Connection TabsConnect Field Wiring in the Electrical Box FIGURE 17 - Field Wiring ConnectionsCAUTION:
Form I-EEDU, Page 21.2 General Installation Information1.0 General1.1 Hazard Labels and NoticesThere are warning labels on the unit and throughout thi
Form I-EEDU, Page 20LOW 1312CRBRBRYOO40 VA. CONTROLBKBL24VLINE VOLTBRRTRANSFORMERYBKBKLIMIT CONTROL2 4CONTACTSVENTER RELAYFOR WIRING)WBK OR RBKBKLINE/
Form I-EEDU, P/N 150492 R6, Page 218.1 Combustion Air Proving Switch8.0 ControlsPressure Switch TableThe combustion air proving switch is a pressure s
Form I-EEDU, Page 22
Form I-EEDU, P/N 150492 R6, Page 23FIGURE 22 - (A) Remote Temperature Selector and (B) Stage-Adder Module - Option AG15(A) (B) 8.4.4 Optional Electro
Form I-EEDU, Page 248.5 Pilot and Ignition SystemsA gas-red intermittent pilot is standard. The vertical pilot is located under the aeration panel on
Form I-EEDU, P/N 150492 R6, Page 259.0 Commissioning and Startup9.1 Check the installation prior to startup:Check suspension. Unit must be secure an
Form I-EEDU, Page 26DANGERThe gas burner in this gas-red equipment is designed and equipped to provide safe, complete combustion. However,
Form I-EEDU, P/N 150492 R6, Page 27Single-Stage Valve1/8" INLET Pressure Tap1/8” Outlet Pressure TapFIGURE 25 - Gas Valve Shutoff CheckInstruct
Form I-EEDU, Page 28FIGURE 27A - Vertical Spark PilotFIGURE 27B - Pilot LocationBurnerRearSupport2-3/4” (70mm)of burnerof pilot and sensor3/4” (±1/3
Form I-EEDU, P/N 150492 R6, Page 29All Sizes -- After cleaning is complete, reverse the procedure to re-assemble the fur-nace. Use extreme care so tha
Form I-EEDU, P/N 150492 R6, Page 31.4 Installation CodesThe duct furnaces covered in this manual are design-certied by the Canadian Stan-dards Associ
Form I-EEDU, Page 30APPENDIXConverting Model EEDU Duct Furnace for Lower Temperature Rise and Higher CFM ApplicationNOTE: If airow is being reversed
Form I-EEDU, P/N 150492 R6, Page 31FIGURE 29 - Discharge Air End of the Heat Exchanger showing the Bafe Assembly to be Removed Conversion is complete
Form I-EEDU, Page 32IndexBTop bafe support 5Heat Exchanger Bafes 30Blower Connections 15Burner Air Adjustment 24Burner Carryover 24Burner Oric
Form I-EEDU, Page 43.1 Uncrating and InspectionThis furnace was test operated and inspected at the factory prior to crating and was in operating condi
Form I-EEDU, P/N 150492 R6, Page 5Heating -- Gas Control OptionOption AG7 - Amplier, P/N 260863; Thermostat, P/N 48033Makeup Air -- Control Options (
Form I-EEDU, Page 63.0 Uncrating and Preparation (cont'd)3.2 Preparing the Furnace for Installation (cont'd)FIGURE 3 - Condensate Drain, Opt
Form I-EEDU, P/N 150492 R6, Page 7FIGURE 4C - Front View of Coupled FurnacesAA + 2" (51mm) Limit ControlLimit ControlSize "A"75-100 14-
Form I-EEDU, Page 84.0 Dimensions & Clearances (cont'd)WARNINGUnits must be level for proper operation. Do not place or add additional weight
Form I-EEDU, P/N 150492 R6, Page 96.0 MechanicalThis appliance is equipped for a maximum gas supply pressure of 1/2 psi, 3.4 kPa, or 14 inches water c