Form I-EEDU, P/N 150492 R6, Page 21
8.1 Combustion Air
Proving Switch
8.0 Controls
Pressure
Switch
Table
The combustion air proving switch is a pressure sensitive switch that monitors air pres-
sure to ensure that proper combustion airow is available. The switch is a single pole
- normally open - device which closes when a decreasing pressure is sensed in the
outlet duct of the ue gas collection box.
On startup when the heater is cold, the sensing pressure is at the most negative level,
and as the heater and ue system warm up, the sensing pressure becomes less nega-
tive. After the system has reached equilibrium (about 20 minutes), the sensing pres-
sure levels off.
If a restriction or excessive ue length or turns cause the sensing pressure to become
less than the switch setpoint, the pressure switch will function to shut off the main burn-
ers. The main burners will remain off until the system has cooled and/or the ue system
resistance is reduced. The Table lists the approximate water column negative pressure
readings and switch setpoints for sea level operating conditions.
DANGER
Safe operation of this unit requires proper venting ow. NEVER bypass combustion air proving
switch or attempt to operate the unit without the venter running and the proper ow in the vent
system. Hazardous conditions could result. See Hazard Levels, page 2.
Start-Up Cold
-1.0" w.c.
Equilibrium
-0.60" w.c.
Set Point "Off"
-0.48" w.c.
Set Point "On"
-0.65" w.c.
Access
to limit
switch
from
"outside"
the
furnace
8.2 Limit Switch
View
of limit
switch
from
"inside"
the furnace
FIGURE 19 -
Access to the
limit switch
depends on the
installation.
A non-adjustable high limit switch mounted at the outlet air side of the heat exchanger
acts to shut off the gas supply in the event of air handler motor failure, lack of correct
airow (See Paragraph 6.3), or restriction due to lters and/or duct design. See FIG-
URE 19 for mounting and service.
Depending on accessibility, the limit switch may be serviced from either the outside of
the unit or from the inside through the access panel in the discharge duct. When units
are installed side by side, the service access panel must be in either the top or bottom
of the ductwork for limit switch service. (See Paragraphs 3.2.3 and 6.3.4.)
8.3 Fan Control
(Optional, Field
Installed)
FIGURE 20A - Installation
of Optional Fan Control Kit,
Option CQ1 (P/N 57960)
WARNING
If you turn off the power
supply, turn off the gas.
See Hazard Levels, page
2.
NOTE: Required with makeup air gas control options; see Paragraphs 8.4.3 and 8.4.4.
1. Fan control provides the following: a) Delay of fan operation preventing circulation
of cold air, and b) Fan operation as long as the unit is hot.
2. The fan control provides additional safety by keeping the fan in operation in the
event that the gas valve fails to close when the thermostat is satised.