Reznor R6GI Unit Installation Manual Manual do Utilizador Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 10
11
Table 2
Pre-Electrical Checklist
Verify the voltage, frequency, and phase of the supply
source match the specifications on the unit rating plate.
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
See Table 2 or the unit wiring label for proper high and
low voltage wiring.
Verify factory wiring is in accordance with the unit
wiring diagram. See Figure 17 (page 34) & Figure
18 (page 35). Verify the connections didn’t loosen
during shipping or installation.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injuryifanelectricalfaultshouldoccur.Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box (next to the terminal block) for grounding
the unit.
Line Voltage
• Thelinevoltagetotheunitshouldbesuppliedfroma
dedicated branch circuit containing the correct fuse or
circuit breaker for the unit.
• A properly sized branch circuit and electrical
disconnect must be located within sight of and
readily accessible to the unit. This switch shall be
capable of electrically de-energizing the outdoor unit.
See unit data label for proper incoming field wiring. Any
other wiring methods must be acceptable to authority
having jurisdiction.
• Useonlycopperwireforthelinevoltagepowersupply
to this unit. See Table 3, (page 12). Use proper
code agency listed conduit and a conduit connector for
connecting the supply wires to the unit. Use of outdoor
shielded conduit (metal lined Sealtite
®
) is recommended.
• Providepowersupplyfortheunitinaccordancewith
the unit wiring diagram and the unit rating plate.
• Removethecontrolpanelcover.Routethepowerand
ground wires (3 wires, including earth ground) from the
disconnect box to the unit.
• ConnectthelinevoltageleadstoL1 & L2 box lugs of
the high voltage terminal block, and the ground wire to
the grounding lug located above the terminal block.
• Replacethecontrolpanelcoverbeforeapplyingpower.
• Overcurrentprotectionmustbeprovidedatthebranch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes.
See the unit rating plate for maximum circuit ampacity
and maximum overcurrent protection limits.
• Awiringdiagramislocatedontheinsidecoverofthe
control access panel of the outdoor unit. The installer
should become familiar with the wiring diagram (Figure
17 & Figure 18) before making any electrical connections
to the outdoor unit.
For 208Volt Operation Only:
• Unitsareshippedfromthefactorywiredfor240volt
transformer operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Theinducermotorlowspeedresistormustbeby-passed
for 208 Volt operation. Remove the insulated quick
connect from one side of the resistor block and connect
to piggyback terminal on opposite side to complete
motor circuit.
Thermostat / Low Voltage Connections
• This Gas / Electric unit is designed to operate with
a 24 VAC Class II control circuit. The control circuit
wiring must comply with the current provisions of the
NEC (ANSI/NFPA 70) and with applicable local codes
having jurisdiction. Thermostat connections should be
made in accordance with the instructions supplied with
the thermostat.
• Theseunitsuseaspecialvariablespeedcompressorto
achieve a high level of efficiency in a compact frame. A
2 stage cooling / 2 stage heating 24V thermostat should
be used with this unit. See Figure 6 (page 12).
24VAC control power wiring must be routed to
interconnect the two-stage thermostat and the the units
low voltage terminal block. Recommended wire gauge
and wire lengths for typical thermostat connections are
listed in Table 4, (page 12).
• Eightwiresmustberuntothecontrolpanel.R, C, W,
W2, G, Y1, Y2, and L (if used) that originate at the
thermostat. Optional L provides a fault indication for
some thermostats.
• Thethermostatshouldbemountedabout5feetabove
the floor on an inside wall. DO NOT install the thermostat
Table 2. Electrical Data
MODEL
NUMBER
(R6GI / PPG2GI)
NOMINAL
COOLING
CAPACITY
(TONS)
MAXIMUM
HEATING
INPUT
NOMINAL
ELECTRICAL
SUPPLY
VOLTAGE RANGE COMPRESSOR
FAN
MOTOR
FLA
INDOOR
BLOWER
FLA
SINGLE CIRCUIT
MIN MAX RLA LRA MCA MOP
E24K080X 2 80,000 208-230/60/1 187 253 11.6 N/A 2.60 3.80 20.9 30.0
E36K100X 3 100,000 208-230/60/1 187 253 16.2 N/A 2.60 3.80 26.7 40.0
E48K120X 4 120,000 208-230/60/1 187 253 17.6 N/A 3.80 7.00 32.8 50.0
E60K120X 5 120,000 208-230/60/1 187 253 24.0 N/A 3.80 7.00 40.8 60.0
NOTE: FLA = Full Load Amps; LRA = Lock Rotor amps; RLA = Rated Load Amps.
Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 39 40

Comentários a estes Manuais

Sem comentários